UK’s trusted IT infrastructure partner since 2003
Servnet
FinanceToolsConfiguratorGet in Touch
FREE UK TOOL · RACK & POWER DENSITY

Will it fit,
and can you power it?

Put in an equipment list — get U, kW, feeds, cooling, weight, floor point load and depth. Sized on BS 7671, not the American 80% rule — and on measured power, not PSU nameplate.

No bogus 80% UK derateA/B feeds counted at 50%SPECpower-measured drawDepth, weight & doorway checks
1048 mm usable mounting depth (1200 mm nominal) · 1700.97 kg static · 1991 mm external height
What goes in it
RACK DESIGN
IT load
3.94 kW
below the ~9 kW 2025 average
Space
18 / 40U
45% used · 22U free
Weight
288 kg
16.9% of 1,701 kg static
Feeds
2 × 32 A
56.3% per feed
Cooling
3.94 kW
13,430 BTU/hr · 1.12 tons
Point load
1.04 kN
105.5 kg per foot
Depth
727 mm
rack allows 1048 mm
Get this rack quoted →
Measured and datasheet figures — confirm the real draw for your exact build. No prices shown here.
42U · 18U used · 22U free510152025303540reserved2U2U2U2U2U2U2U2U1991 mm external · 1048 mm mounting depth
ServersGPU / AINetworkStoragePower
The electrical working
  • 32 A single-phase (IEC 60309)7.36 kVA nameplate (V × A).
  • Regional derate 1.00 — BS 7671 has no 80% continuous-load rule; power factor 0.956.99 kW usable.
  • A/B redundancy: 2 feeds, but usable load is one feed's capacity — each carries 3.94 kW (56.3%).
  • Cooling is 1:1 with IT load (3.94 kW) — no 1.3× uplift, because the electrical energy entering the rack leaves it as heat.
  • Point load = 422.1 kg gross ÷ 4 feet = 105.5 kg = 1.04 kN.
The same 32 A / 230 V circuit, sized two waysNameplate 7.36 kVA (230 V × 32 A)UK / IEC (BS 7671)7.36 kVA100% of rating — no continuous-load derate existsUS / NEC (210.19)5.89 kVA80% = 1 ÷ 1.25 continuous-load ruleUK with A/B feeds7.36 kVAper feed — each carries all of it on failoverApplying the US 80% factor to a UK circuit strands 1.47 kVA — one fifth of every circuit you pay for.
BS 7671 requires only that Ib ≤ In ≤ Iz and I2 ≤ 1.45 × Iz — there is no 80% continuous-load factor anywhere in it, and BS EN 60898-1 MCBs are calibrated to carry 100% of their rating continuously. The clearest proof is a single product: APC sells one PDU as “22.1kW 400V 32A or 17.3kW 415V 30A”— identical hardware, described under two regional conventions. NVIDIA’s DGX SuperPOD design guide publishes an explicit “Breaker Derating” column: 100% for IEC, 80% for NEC.
2U 2-socket server (HPE DL380 Gen11 class) is a three-person lift
33 kg fully populated.
A/B feeds: each runs at 50%, not 100%
With two feeds, usable IT load is the capacity of ONE feed — either must carry everything when the other fails. 1 × 32 A single-phase (IEC 60309) gives 6.99 kW usable, not 13.98 kW. Apply the same 50% test to every element in the path: UPS, floor PDU, breaker, whip and rack PDU.
UK/IEC circuits are rated at 100%
BS 7671 has no 80% continuous-load rule — it requires only Ib ≤ In ≤ Iz and I2 ≤ 1.45 × Iz. BS EN 60898-1 MCBs carry 100% of their rating continuously. The 80% figure so often quoted is the US NEC (1 ÷ 1.25) and applying it here would under-size this design by 20%.
Rack is taller than the doorway
APC NetShelter SX 42U 600×1200 (AR3300) is 1991 mm externally, against a 1981 mm door. Every standard 42U cabinet (1991–2006 mm) exceeds the 1981 mm England & Wales internal door. The rack may need to go in on its side or be built in place — and door LEAF height is not the structural opening height, so measure the actual opening before delivery.
Where these numbers come from
Server power is SPECpower-measured where a measurement exists, and vendor datasheet maximum where it does not — never PSU nameplate, which routinely doubles the real figure. Rack dimensions use maximum mounting depth, not the nominal depth on the box. Raised-floor classes are ultimate loads and are divided by a safety factor before use.
Get this rack quoted
We'll confirm the real power draw for your build, check rails, depth and door access, and quote the cabinet, PDUs and install from UK stock. No obligation.

Indicative illustration only. Servnet Limited is not authorised or regulated by the FCA and does not provide financial advice or arrange finance. All finance opportunities are referred to Number Eight Business Finance. Finance policy

Most UK rack designs are quietly built to an American rule

Ask almost any rack calculator how much load a 32 A circuit will carry and it will apply an 80% factor. That factor is real, but it belongs to the US National Electrical Code, which requires circuits to be sized at 125% of a continuous load — 80% is just 1 ÷ 1.25 read backwards. BS 7671 contains nothing equivalent. It asks only that design current ≤ protective device rating ≤ cable capacity, and BS EN 60898-1 MCBs are calibrated to carry their full rating continuously. Applying the American factor to a British installation throws away a fifth of every circuit before you have plugged anything in.

The evidence is not subtle. APC sells a single PDU described as “22.1kW 400V 32A or 17.3kW 415V 30A”— the same hardware, quoted under two regional conventions. NVIDIA’s DGX SuperPOD data-centre design guide publishes an explicit breaker-derating column: 100% for IEC, 80% for NEC. Vertiv’s EMEA rack-PDU nameplates are full V × I. This planner keeps the two conventions apart: pick a UK/IEC circuit and you get its full rating; pick a North American one and the 80% factor is applied, and the reasoning is shown either way.

What genuinely reduces UK capacity

Three things, none of them a flat percentage. Ambient temperature: MCB trip current falls as the enclosure heats, on a published curve — a 16 A device gives 16.0 A at 30 °C and about 12.2 A at 60 °C. A/B redundancy: two feeds are not twice the power, because either has to carry the whole rack when the other fails, so each normally runs at 50%. And power factor, which converts the circuit’s apparent power in kVA into the real power in kW your equipment actually consumes. The planner applies all three explicitly and shows the arithmetic, so you can check it rather than trust it.

Seven ways rack planning goes wrong

Each is checked automatically by the planner above.

01
Applying the US 80% rule to a UK circuit

BS 7671 has no continuous-load derate. It requires Ib ≤ In ≤ Iz and I₂ ≤ 1.45 × Iz, and BS EN 60898-1 MCBs carry 100% of their rating continuously. The 80% figure is the US NEC (1 ÷ 1.25). Applying it here strands a fifth of every circuit you pay for — on a 32 A feed that is 1.47 kVA gone for nothing.

02
Treating A/B feeds as double the capacity

Two feeds do not give you twice the power. Either one has to carry everything when the other fails, so usable IT load is ONE feed’s capacity and each normally runs at 50%. The same test applies to every element in the path — UPS, floor PDU, breaker, whip and rack PDU.

03
Using PSU nameplate as the power figure

A pair of 800 W supplies is not a 1,600 W server. Redundant PSUs share one load, and the real draw is far below nameplate — a measured DL380 Gen11 pulls about 439 W at typical load against a much larger plate. This planner uses SPECpower measurements where they exist and vendor maximums where they do not, and says which is which.

04
Sizing cooling with a 1.3× uplift

Cooling at the rack is 1:1 with IT load. Essentially all the electrical energy entering a rack leaves it as heat, so 8 kW of IT is 8 kW of heat — about 27,300 BTU/hr. Uplift factors belong to plant-level design (PUE, UPS and distribution losses), not to the rack itself, and adding them twice is how rooms get over-cooled.

05
Trusting the nominal rack depth

A cabinet sold as 1200 mm deep does not give you 1200 mm to mount in — the APC NetShelter SX AR3300 has 1048 mm of usable mounting depth, because doors and frame take the rest. A 911 mm GPU chassis plus a 0U PDU in the rear channel can fail to fit a rack the datasheet says is plenty deep.

06
Designing a raised floor to its class figure

BS EN 12825 floor classes are ULTIMATE loads, not working loads. You divide by a safety factor of 2 or 3 before designing to them. A rack whose feet look comfortably inside the class number can be well past the working load once the factor is applied — and it is four small feet carrying the whole mass.

07
Forgetting the rack has to get through the door

Every standard 42U cabinet is 1991–2006 mm tall externally, and the standard internal door in England and Wales is 1981 mm (Scotland 2040 mm). The rack does not fit through upright. It goes in on its side or gets built in place — and door leaf height is not the structural opening height, so measure the opening before delivery day.

Circuit capacity reference

Nameplate kVA is V × A single-phase, √3 × V × A three-phase. Usable kW applies the regional derate and a 0.95 power factor. UK/IEC derate is 1.00; North American is 0.80.

CircuitPhasesNameplate kVADerateUsable kW @ PF 0.95
13 A single-phase (BS 1363)Single2.991.00 (BS 7671)2.84
16 A single-phase (IEC 60309)Single3.681.00 (BS 7671)3.50
32 A single-phase (IEC 60309)Single7.361.00 (BS 7671)6.99
63 A single-phase (IEC 60309)Single14.491.00 (BS 7671)13.77
16 A three-phase 400 V (IEC 60309)Three11.091.00 (BS 7671)10.53
32 A three-phase 400 V (IEC 60309)Three22.171.00 (BS 7671)21.06
63 A three-phase 400 V (IEC 60309)Three43.651.00 (BS 7671)41.47
20 A single-phase 208 V (NEC)Single4.160.80 (NEC)3.16
30 A single-phase 208 V (NEC)Single6.240.80 (NEC)4.74
30 A three-phase 208 V (NEC)Three10.810.80 (NEC)8.21
60 A three-phase 208 V (NEC)Three21.620.80 (NEC)16.43

With A/B feeds, usable IT load is one feed’s figure, not the sum. Verified against: EIA-310 / IEC 60297 · ABB · NFPA 70 (NEC) 2023 · APC APDU10350ME · NVIDIA DGX SuperPOD H100 Data Center Design Guide · Vertiv Geist rack PDU brochure · Raritan (Legrand) · Hager · IET Wiring Matters 96 · Uptime Institute Global Data Center Survey 2025 · HPE ProLiant DL360 Gen11 QuickSpecs · HPE ProLiant DL380 Gen11 QuickSpecs · SPEC SPECpower_ssj2008 · Dell PowerEdge R760 Technical Guide · Dell PowerEdge R760xa Technical Guide · Dell PowerEdge XE7745 Technical Guide · Dell N3248 switch family · Dell PowerVault ME5084 · APC NetShelter SX AR3300 · Vertiv VR rack · UK standard internal door heights · BS EN 12825.

Rack power & space FAQs

How many kW can a rack take in the UK?

It is set by the circuit, not by the rack. In the UK a 32 A single-phase 230 V feed is 7.36 kVA nameplate, and BS 7671 lets you use all of it — at 0.95 power factor that is about 6.99 kW per feed. A 32 A three-phase 400 V feed is 22.2 kVA. With A/B redundancy the usable IT load is one feed's capacity, because either must carry the whole rack when the other fails. For context, Uptime Institute's 2025 survey puts the average of modal rack densities at around 9 kW, and more than 80% of operators have no racks above 30 kW — so a 20 kW rack is unusual and a 40 kW rack needs containment or liquid cooling and a room that can genuinely deliver it.

Do I need to derate a UK circuit by 80%?

No — and this is the single most common error in UK rack design. The 80% continuous-load factor comes from the US National Electrical Code, which requires circuits to be sized at 125% of the continuous load; 80% is simply 1 ÷ 1.25. BS 7671 contains no equivalent rule. It requires only that design current ≤ device rating ≤ cable capacity, and that the fusing factor condition holds, and BS EN 60898-1 MCBs are calibrated to carry 100% of their rating continuously. The clearest proof is a single product sold under both conventions: APC lists one PDU as "22.1kW 400V 32A or 17.3kW 415V 30A" — identical hardware, two regional readings. NVIDIA's DGX SuperPOD design guide publishes an explicit breaker-derating column: 100% for IEC, 80% for NEC.

What does derate in the UK, then?

Ambient temperature. MCB trip current falls as the enclosure gets hotter — a 16 A device is good for 16.0 A at 30 °C but around 12.2 A at 60 °C. That is a genuine physical derating with a published curve, and the planner applies it when you raise the ambient above 30 °C. It is quite different from a flat 80% factor: it reflects the actual conditions in your comms room rather than a rule imported from another country's wiring code. Grouping factors and BS EN 61439-3 rated diversity are separate again — diversity is a simultaneity assumption about how many circuits run at once, not a continuous derate on each one.

How much cooling does a rack need?

The same as its IT load, in kW. Essentially all the electrical energy entering a rack leaves it as heat, so an 8 kW rack produces 8 kW of heat — 27,297 BTU/hr, or about 2.27 refrigeration tons. There is no 1.3× uplift at the rack. Uplift factors apply at plant level, where UPS losses, distribution losses and the cooling plant's own consumption are counted (that is what PUE measures), and applying them at both levels double-counts. The one addition worth making at the rack is UPS self-heat if the UPS lives in the same cabinet, which this planner adds to cooling but keeps out of the IT load.

How much weight can a rack hold?

It depends on the cabinet and on whether it is standing still. An APC NetShelter SX AR3300 is rated 1700.97 kg static but 1020.58 kg dynamic — the lower figure is what you may roll it at when populated, and a transport rating is lower again. Open four-post frames cap out around 907 kg and adding a centre rail does not raise that. Individual boxes matter too: over about 34 kg you need enhanced slide rails, at 54.9 kg you are into mechanical-lift territory, and at 90.7 kg a heavy-component support kit is specified. The planner flags each of these per item, because they apply to the box being lifted, not to the rack total.

What is rack point load and why does it matter?

A loaded rack puts its entire mass onto four small feet, so the load on the floor is highly concentrated. Point load is gross weight (equipment plus the rack's own tare) divided by the number of support points, expressed in kN. On a raised access floor this is the number that matters, and the trap is that BS EN 12825 floor classes are ultimate loads: you divide by a safety factor of 2 or 3 to get the working load before comparing. A rack that looks fine against the class figure can be well past the working load. Where the point load is too high, a spreader plate distributes it — but that is a design decision to make before the rack arrives, not after.

Will a 42U rack fit through a standard door?

Not upright. A 42U cabinet is 1991–2006 mm tall externally and the standard internal door height is 1981 mm in England and Wales, 2040 mm in Scotland. The rack goes in on its side, or it is built in place from a flat-pack. Two related traps: the door leaf height is not the structural opening height, so measure the actual opening; and lift dimensions, corridor turning circles and floor loading en route matter as much as the door. The planner flags the doorway check automatically because it is the constraint most often discovered on delivery day.

What is 1U in millimetres?

Exactly 44.45 mm (1.75 inches), from EIA-310 / IEC 60297 — the universal hole spacing of 0.625 in, 0.625 in and 0.500 in sums to 1.75 in per U. Every calculation here uses 44.45 mm rather than a rounded 44 or 45 mm, because over 42U the rounding error is more than a full U. Note also that 0U equipment such as vertical rack PDUs consumes no mounting U but does take roughly 46–51 mm of rear channel depth, which competes with deep chassis for the same space.

💷 Spread the cost · IT finance

Spread the cabinet, power and kit

Racks, PDUs, UPS and the servers that go in them on hire purchase, lease or subscription for UK businesses — one level monthly cost for the whole build.

Calculate monthly payments

Indicative estimate · subject to change · no credit check at this stage · hire purchase, lease & subscription for UK businesses

Indicative illustration only. Servnet Limited is not authorised or regulated by the FCA and does not provide financial advice or arrange finance. All finance opportunities are referred to Number Eight Business Finance. Finance policy

Plan the rest of the build

Talk to a UK specialist

Get expert advice or a no-obligation quote — servers, storage, networking, maintenance, finance and cloud. We reply the same working day.

or call 0800 987 4111