Composable GPU Deployment Checklist: 14 Pre-Install Checks — analysisComposable GPU Deployment Checklist: 14 Pre-Install Checks — analysis — reach
AI Infrastructure

Composable GPU Deployment Checklist: 14 Pre-Install Checks

Servnet Editorial · IT infrastructure analysis9 min read
Share

Most composable GPU projects that stall do so on something mundane: a server that needs a special riser, a PDU with the wrong inlets, a chassis deeper than the rack, a GPU chassis that wants cooler air than the hall delivers. None of these appear on a product brochure. This checklist pulls them out of Liqid’s datasheets, compatibility list and support terms, so they can be settled before the hardware is ordered, not when it arrives.

Liqid composable GPU pre-install checks
Liqid install readiness — control map1-3Server and GPU on HCL, with footnotesCORE4Free x16 slot (Gen5) + PCIe native BIOSCORE5Linux, VMware/Nutanix or WS 2012 R2+CORE6Rack depth for 790 mm chassisCORE7Saf-D-Grid 400 V PDU outletsCORE8Inlet air at or below 27 °CCORE9Rack power (~22 kW typical, 30-GPU MI350P)PLUS10-11CDFP cabling + management networkPLUS12UK-morning first-line support planPLUS13-14Licence term + scheduler versionsOPT

Compatibility: servers and GPUs

Liqid publishes a hardware compatibility list (HCL). The revision dated 17 August 2026 has 49 server entries and 47 GPU entries, and several carry conditions in footnotes. Those footnotes are where builds go wrong.

  • •1. Host model on the HCL. Dell PowerEdge has 21 entries; Cisco UCS, Fsas PRIMERGY, HPE ProLiant DL380 Gen10, Lenovo SR655 and Supermicro are also listed. Dell R650, R650xs, R750 and R750xs need a special riser configuration with Dell custom BIOS; Cisco UCS C240 M5 works at PCIe Gen3 only.
  • •2. GPU model on the HCL, with its enclosure condition. The H200 NVL is supported only on select Gen5 enclosures; the H100 only on the updated Gen4 10-slot enclosure; the L40S needs a firmware update on the Gen4 EX-4410.
  • •3. GPU form factor. Cards must be PCIe, up to full-height, full-length and double-wide; the Gen5 EX-5410P supports 600 W devices.
  • •4. For Liqid’s current Gen5 fabric, a free PCIe Gen5 x16 slot in each host for the half-height HX-5160P-1C adapter (27 W maximum), plus PCIe native mode in the BIOS. Older listed hosts use Liqid’s Gen3/Gen4 adapters.
  • •5. Host operating system. Linux, VMware/Nutanix, or Windows Server 2012 R2 or later; desktop Windows is not supported. The Gen5 adapter supports surprise hot-plug under Windows and Linux.

Facility: space, power and air

Liqid’s chassis are datacentre equipment with their own requirements, and some differ from the servers beside them.

  • •6. Rack depth. The EX-5410P and EX-5410C are 4U and 790 mm deep (175 × 447 × 790 mm). The EX-5410P weighs 34.34 kg.
  • •7. Power inlets. The EX-5410P has four 3,000 W Titanium supplies with Saf-D-Grid 400 V connectors and accepts 100–277 VAC. Check your PDUs have matching outlets, or plan for new ones.
  • •8. Inlet temperature. The EX-5410P is specified for 0 to 27 °C operation, while the EX-5410C and Liqid’s switches are specified to 35 °C. If your cold aisle runs warmer than 27 °C, address that first.
  • •9. Total load. A 30-GPU UltraStack MI350P draws about 22 kW, air-cooled; GPU power alone is 600 W per MI350P. Plan the rack in our rack power density planner.

Fabric: cabling and management

The fabric is a second network to plan alongside your Ethernet.

  • •10. Cable type and length. Liqid uses CDFP connectors, in copper for short runs or active optical cable (AOC) for longer ones. AOC can take an FX-5016-2 switch from about 225 W typical to 400 W or more.
  • •11. Management connectivity. The EX-5410P has two Gen5 x1 and two 10GbE management ports plus a BMC; every validated bundle includes a 1U Liqid Director appliance that needs rack space and a management connection.
A SmartStack 30+ rack, top to bottom
5Gen5 ToR switches2 × 18-port Gen5 x16 top-of-rack switches4Liqid Director1U management appliance running Matrix3EX-5410P chassis × 34U each, 30 GPU slots, 790 mm deep2Host serversUp to 16, one Gen5 HBA each1Power and coolingSaf-D-Grid PDUs · inlet air ≤27 °C
View the data behind this chart
A SmartStack 30+ rack, top to bottom
LayerDetail
Gen5 ToR switches2 × 18-port Gen5 x16 top-of-rack switches
Liqid Director1U management appliance running Matrix
EX-5410P chassis × 34U each, 30 GPU slots, 790 mm deep
Host serversUp to 16, one Gen5 HBA each
Power and coolingSaf-D-Grid PDUs · inlet air ≤27 °C

Operations: support, licences and software

The commercial and operational terms deserve the same scrutiny as the hardware.

  • •12. Support hours. Liqid’s standard support runs Monday to Friday, 8am to 5pm US Mountain time, which is roughly 15:00 to midnight in the UK for most of the year (14:00 to 23:00 for a few weeks in March and late October, when the clocks change on different dates). Standard support has no after-hours or holiday cover, and work stops at 5pm Mountain time. Separately, Liqid’s phone line pages an on-call engineer for out-of-hours system outages, and its severity table targets a one-hour response for Severity 1. Decide who takes the first call during the UK morning.
  • •13. Licence and warranty terms. Liqid publishes no general Matrix licensing model: its MI350P system includes a three-year slot licence, and SmartStack bundles carry 36- or 60-month software and hardware support. Match the terms to your planned life for the system.
  • •14. Orchestration fit. Liqid lists compatibility with Kubernetes, Slurm, OpenShift, VMware and Ansible. Confirm the versions you run, and plan how jobs release GPUs before Matrix reassigns them.

Order the checks to save time

Run the list in this order: compatibility first, because an unlisted server or GPU changes the whole design; facility second, because power and cooling changes have the longest lead times; fabric and operations last. Our Liqid compatibility summary covers the first block by vendor, and the fabric hardware page has the chassis and switch specifications in one place.

If you would rather hand the list over, send us your server models, GPU plans and rack details. We check each item against Liqid’s current documents and come back with a sized, quoted design. Start on the Liqid page.

Share
Key takeaways
  • ✓Check every server and GPU against Liqid’s HCL footnotes: some need special risers, BIOS or a specific enclosure generation.
  • ✓For the current Gen5 fabric each host needs a free Gen5 x16 slot and PCIe native mode in BIOS, running Linux, VMware/Nutanix or Windows Server 2012 R2 or later.
  • ✓Liqid’s EX-5410P and EX-5410C chassis are 790 mm deep and use Saf-D-Grid 400 V power connectors, and the EX-5410P is rated only to 27 °C.
  • ✓Liqid’s standard support hours fall roughly 15:00 to midnight UK time for most of the year; plan UK-morning first-line cover.
  • ✓Run compatibility first, facility second, fabric and operations last.
Frequently asked

FAQs — Composable GPU Deployment Checklist

Before ordering

What is the most common blocker for a Liqid install?

Compatibility conditions. Several servers on Liqid’s list need a special riser or custom BIOS, and some GPUs are supported only in specific enclosure generations. Check footnotes first, using our compatibility summary, before planning anything else.

Does a Liqid GPU chassis need special power?

Its supplies use Saf-D-Grid 400 V connectors: four 3,000 W Titanium PSUs on the EX-5410P, accepting 100–277 VAC. Many existing PDUs do not have those outlets, so check early and size circuits with our watts, amps and VA calculator.

Running it

What support hours does Liqid offer?

Standard support is Monday to Friday, 8am to 5pm US Mountain time (roughly 15:00 to midnight UK time for most of the year), with no after-hours or holiday cover. Separately, Liqid’s severity table targets a one-hour response for Severity 1, and its phone line pages an on-call engineer for out-of-hours outages. Plan who handles first-line issues during the UK morning.

Can the GPU chassis share a hot aisle with servers?

Physically yes, but check temperature. The EX-5410P is rated for 0 to 27 °C operation, lower than many servers. If your inlet air runs above 27 °C, fix containment or cooling first; our cooling calculator helps size it.